Ceramic Tile Institute of America


login
   
  Search
   














Find a supplier Find a Contractor


Better Business Bureau


State Licensing Boards

Whats new at thetiledoctor

Tile Glossary of Terms

Tile Calculator


 
 

Steam/Frig How-To

fr4     

Welcome to Steam and Refrigeration rooms. This section will detail the application of ceramic or stone tile in these areas. These projects are complicated and require many technical elements not found in general residential and commercial projects.

Dr's tip: As always, follow the Manufacturers recommendations for all the products you plan to use steam rooms or refrigeration rooms. These projects need to comply with federal, state, and local building codes.

 

 

 

Steam rooms and refrigeration rooms are similar, in construction, to shower room construction. They are similar, as they will generally include tiled walls, ceilings, and tiled floors. The floors, for example, will generally include a shower type drain.

They differ greatly from normal shower construction in several areas. The first difference is the requirement for a continuous waterproof membrane on all sides of the construction. They sometimes require that insulation be a part of the wall construction. They also require the addition of a sealed open slip joint at the point where the walls meet the ceiling.

Additionally in steam rooms, the ceiling should be sloped 2” per foot to keep hot water from dripping on the occupants.  The slope can be directed to one wall or toward the center.

Let's examine each of these additional requirements. The continuous waterproof membrane is required due to the water vapor transmission inherent to steam rooms. The steam can penetrate the tiled surfaces and flow into adjoining areas. 

Insulation is required in stream rooms where a type of waterproofing is desired that will not withstand the heat generated. In refrigeration rooms the necessity for the insulation is obvious. Speaking of insulation, the tie wires and pencil rod is an additional feature not found in traditional shower construction.

The tie wire and pencil rod is the fastening device used to secure the metal lath or reinforcement since nails and staples cannot be used. The tie wires and pencil rod are used only when a scratch coat and mortar bed are used. When the tie wire and pencil rod system is used, the penetration of the membrane must be sealed satisfactorily to keep the membrane continuous and waterproof.

The sealed open slip joint refers to a detail that isolates the ceiling from the walls to compensate for excessive expansion and contraction from extremes in temperature. 

Note that for mortar bed steam rooms, a sealed open slip joint is required in walls that exceed 16 feet in length.

STEAM ROOMS

FigAC9

In Figure A we see a cement mortar or thick bed installation. This project would start by applying the waterproof membrane over the framing members per the Manufacturers instructions for the desired membrane. The waterproof membrane is to be continuous throughout the installation and should be applied over a pre-sloped floor terminating into a two-piece type shower drain. The pre-slope of the floor, like the finished floor, should slope ¼ per foot to the drain.

If insulation is required for the membrane, the insulation should be applied over the membrane. The tie wires are then fastened through the insulation and membrane. The holes created by the fastening of the tie wires should then be sealed.

Next, ¼ pencil rod is attached vertically using the pencil rod. The 2.5 min. metal lath is then attached to the pencil rod using tie wires. The lath should be applied to the walls and ceiling cut at all corners and slip joints including any slip joints in wall areas exceeding 16 feet in length.

Dr's tip: Caution should be exercised to not puncture the membrane during each step of the construction process while the membrane is exposed.

 

 

 

The scratch coat of wall mortar is then applied to the walls and ceiling being sure to terminate the mortar at any required joints. Following the curing of the scratch coat, the brown or final coat of wall mortar covers the scratch coat on walls and ceiling. This final thickness of the wall and ceiling mortar should be ¾ to 1.

The floor mortar can be installed at this point and should be reinforced with 2” X 2” 16/16 wire or its equivalent. Be sure to keep the weep holes open at the drain with crushed tile or stone.

Tile can be installed with Portland cement paste on a mortar bed that is still workable or using dry set/latex Portland cement mortar on a cured bed. This is eventually followed by Portland cement grout.

Note: The slip joint should be constructed to allow rounded back-up filler made of compressible closed cell polyethylene or its equivalent that will not bond to the sealant used to cover it. The Manufacturers recommendations should be followed for the products and joint construction that are desired for use.

To review the section on expansion joints click here.

For more on mortar beds visit Walls.  Other mortar bed installations can be found under Tubs or Showers. A scratch coat mortar bed application can be seen by clicking here

FigBC9

In Figure B, we see a steam room constructed using backer board or thin set installation instead of a mortar bed. The Manufacturer must recommend the desired backer board for use in steam room applications.

Since the backer board must be applied directly over the membrane, the membrane must be able to withstand the heat generated in the steam room. Also, the membrane needs to be self sealing as the backer board fasteners will puncture it during fastening.

The membrane can be positioned either over the framing members or over the backer board itself.

Note: In a backer board steam room installation, the installer must comply with the Manufacturers recommendations for the desired products.

The tile installation mirrors that of the mortar bed steam room including the floor mortar process.

REFRIGERATION ROOMS

FigCC9

In Figure C, we see a refrigeration room. This is a mortar bed or thick bed installation very similar to the mortar bed steam room. The framing members and concrete substrate are behind the insulation and are not shown in the drawing.

The key differences here are that the insulation is an integral part of the design.

Frost proof tile must be selected for this project.

Also note that the reinforced concrete floor must be installed over the insulation. For floors subject to forklifts, a 4” thick slab should be used.

Keep an eye on this section for how to photos and more information.

home | newsletter | terms of service | links | contact | site map